Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM05486
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2002 | ELECTRIC - INTERMEDIATE | Approved | 1.) INSPECTION ON 2 CAR DETACHED GAR. OK THANKS | |
02/04/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*APPROVED NOTE DETACHED GARAGE NOT INCLUDED. | |
01/30/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1.) REMOVE LOW VOLTAGE DOOR BELL WIRING FROM THE INTERIOR OF THE 110V J box 2.) INSTALL GROUND WIRE PIGTAILS FOR ALL SWITCHES. BOXES WITH THE METAL GROUND SRAP DO NOT NEED A PIGTAIL. 3.) INSTALL A "FAN" BOX IN 2ND FLR. BEDROOM CIELING. 4.) PROVIDE FLEX CONDUIT SLEEVE FOR A/C FEEDER ROMEX OR INSTALL 'J' BOX IN WALL. CABLE CANNOT BE EXTENDED UNPROTECTED TO UNIT. |