Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2002 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 04/02/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK 2-1" PVC FROM BUILDING OUT AND EAST FOR GATE OK 1-1" PVC FROM BUILDING OUT AND WEST FOR 2 CARPORTS OK TEMP CABLES |
| 01/27/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK2-1" PVC. OK 1-2 PVC OK 1-4" PVC. UNDER DATA ROOM |
| 01/13/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK 3-4/0 XHHW FROM EAST END BUILDING #5 TO WEST END BUILDING #7 IN TRENCH WITH SHADING FOR TEMP POWER. |
| 01/09/2002 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*1.) CONDUCTORS TO BE LISTED FOR DIRECT BURAL AS PER CODE XHHW IS NOT LISTED. |
| 01/08/2002 |
ELECTRIC - UNDERGROUND |
|
Not ready for Inspection |
IVRS - Inspection 0000* |