Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/11/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR 3013 A' NEW METER OK C OF O. |
| 01/09/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/04/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) METHOD OF ATTACHMENT OF LUGS IN TERMCABINATE NOT AN APPROVED METHOD OF DOUBLE NUTTING LUGS TO BOLT STUDS, SEE INSTALLATION LISTING FOR MECH. LUGS USED. 110-3,110-12 NEC. 2.) EQUIPMENT GROUND MUST BE EFFECTIVELY BONDED TO METER NEW ENCLOSURE. BONDING TO BOND BUSHING ALONE IN NOT SUFFICIENT, MUST BE BONDED TO ENCLOUSURE, 250-92 (2). 3.) INSTALL GROUND BAR IN PANEL INSIDE FOR BRANCH CIRCUIT GROUNDING, DBL LUGGING NOT APPROVED. 4.) INSTA HOT IN BATHROOM NOT WIRED YET. |