Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM05467

Parcel: 12308007C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM05467

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/11/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR 3013 A' NEW METER OK C OF O.
01/09/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
01/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) METHOD OF ATTACHMENT OF LUGS IN TERMCABINATE NOT AN APPROVED METHOD OF DOUBLE NUTTING LUGS TO BOLT STUDS, SEE INSTALLATION LISTING FOR MECH. LUGS USED. 110-3,110-12 NEC. 2.) EQUIPMENT GROUND MUST BE EFFECTIVELY BONDED TO METER NEW ENCLOSURE. BONDING TO BOND BUSHING ALONE IN NOT SUFFICIENT, MUST BE BONDED TO ENCLOUSURE, 250-92 (2). 3.) INSTALL GROUND BAR IN PANEL INSIDE FOR BRANCH CIRCUIT GROUNDING, DBL LUGGING NOT APPROVED. 4.) INSTA HOT IN BATHROOM NOT WIRED YET.