Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05467
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR 3013 A' NEW METER OK C OF O. | |
01/09/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
01/04/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) METHOD OF ATTACHMENT OF LUGS IN TERMCABINATE NOT AN APPROVED METHOD OF DOUBLE NUTTING LUGS TO BOLT STUDS, SEE INSTALLATION LISTING FOR MECH. LUGS USED. 110-3,110-12 NEC. 2.) EQUIPMENT GROUND MUST BE EFFECTIVELY BONDED TO METER NEW ENCLOSURE. BONDING TO BOND BUSHING ALONE IN NOT SUFFICIENT, MUST BE BONDED TO ENCLOUSURE, 250-92 (2). 3.) INSTALL GROUND BAR IN PANEL INSIDE FOR BRANCH CIRCUIT GROUNDING, DBL LUGGING NOT APPROVED. 4.) INSTA HOT IN BATHROOM NOT WIRED YET. |