Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM05460
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*CORRECTION APPROVED. | |
10/31/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*CONDENSATE CANNOT TERMINATE INTO A SEWER WASTE VENT. GO TO WITHIN 6" OF THE GROUND. 2.) CANNOT OPEN ELEC. DISCONNECT TO VERIFY FUSES. DISCONNECT IS PAINTED SHUT. RECALL FOR INSPECTION. 3.) PROVIDE AN OUTSIDE AIR VENT ON AC UNIT AS PER PLANS. |