Permit: T01CM05450


Addresses:

2 W GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM05450

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*OK WALLS FINISH WORK ABOVE CEILING CHECK M/C CABLE STRAPING WITHIN 12" OF BOXES.