Permit: T01CM05420

Parcel: 120084890


Addresses:

4725 S 12TH AV #111

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/10/2002 ELECTRIC - FINAL Approved PER ARMANDO.
06/06/2002 ELECTRIC - FINAL Partial Approval SUBJECT TO OTHER INSPECTION NO POWER CLEARANCE UNTIL ALL SIGNED.
06/05/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*NEED ACCURATE PLAN DEPICITNG FEEDER TAP FOR SUB PANEL 8 1/2 X 11 OK . LETTER EXPLAINING CHANGE OF LOCATION FOR PANEL "F" FRAN WEST WALL TO EAST WALL.
06/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*DENIED FINAL WILL BE SUBJECT TO OTHER INSPECTORS. 1.) LICENSED CONTACTOR IS MAJOR ELECTRIC JOE 2.) NEW PANEL BOARD IS USING A COMON GROUND BAR FOR BOTH THE NEUTRALS AND GROUNDS. 3.) BOND ALL BOXES AND BOND PANEL BOARD. 4.) MUST HAVE 2 MORE SCREWS ON IND. RAISED RECEPT. DEVICES. 5.) MUST HAVE LIGHT IN BATHROOM. 6.) PLEASE REVISE PLAN AND SHOW CORRECT LOCATION OF NEW PANEL F 7.) FINISH WATER HEATER 8.) PERMANENTLY MARK SERVICE DISCONNECT SUITE 111. AND DOWNSTREAM EQUIP. IT JB AND PANEL BOARD. 9.) MUST REVISE AS BUILT FEEDER AND SUBMIT W/#6 ABOVE. SHOW TAP RULE, FUSING ETC. 10.) 2/0 FEEDER, 11.
05/22/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*