Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM05406

Parcel: 136231200


Addresses:

6956 E VERNICE ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T01CM05406

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
04/03/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/02/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
11/01/2001 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) GAS PRESSSURE TEST-OK 2) CANNOT USE FLEX FOR T & P LINE, MUST BE FULL SIZE 3/4" PIPE 3) T & P 90 DEGREE ELBOW AT EXTERIRO IS BELOW GRADE, NEED SMALL DRY WELL 4) REMOVE TAPE AT DOUBLE-SINGLE WALL FLUE, USE SCREWS 5) T & P VALVE STICKS WATER KEEPS RUNNING 6) PLEASE LEAVE PERMIT ON SITE