Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T01CM05386
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2002 | MECHANICAL - HOODS | Approved | IVRS - Inspection 0000*CONDENSATE DRAIN LINES DO NOT HAVE ADEQUATE SLOPE. PROVIDE MIN 1/8 PER FT. NEED TO SEE CONDENSATE FROM WALK IN COOLER. GREASE DUCT WRAP IS OK WILL CHECK CORRECTION ON FINAL. OK FOR CEILING TILES. | |
| 10/16/2002 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*16 GA. EXHAUST DUCT OK OK TO WRAP CLOSING F MASTER SINGLE LAYER WRAP. |