Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/18/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 10/17/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) 2 X 4 LAY IN FIXTURES REQUIRE 2 SCREWS 1.) EACH END PER NEC. 2.) COMPLETE ALL TERMINATIONS, 3.) SUPPORT EMT WITHIN 3' OF J-BOXES ART 348-13NEC. 4.) SUPPORT MC CABLE WITHIN 12" OF TERM, EXCEPT 6' OR LESS ART 334-10NEC. 5.) J-BOX FOR OUTLETS CANNOT BE SOLEY SUPPORTED TO GRID, SUPPORT TO STRUCTURE. ART 370-NEC. |
| 10/14/2002 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*SENT TO TEP ON 10/15/02 AT 9:15 AM. |