Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/07/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/04/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) DWV WATER TEST FAILED 2) WATER HEATER VENT TO CLOSE TO ROOF SHEATHING (MINIMUM 1" REQUIRED), FRAMING WITHELD PENDING OTHER INTERMEDIATE INSPECTION |
| 01/02/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |