Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM05364

Parcel: 141130120

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM05364

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/29/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*NEC SECT. ART. 300 PROHIBITS SUPPORTING CABLE OR CONDUIT FROM OTHER CABLES, OR CONDUIT. INSTALL SEPARATE SUPPORT WIRES FOR MC CABLE ABOVE CIELING. INSTALL SEPARATE SUPPORT WIRE FOR MC CABLE ABOVE CEILING. INSTALL SEPARATE SUPPORT WIRES FOR MC CABLE ABOVE CIELING. USE WIRE OTHER THAN REGULAR BUILDING (THHN1)WIRE. USE STAPLES AND PIPE STRAPS.
03/19/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) THIS PROJECT IS INSPECTED AND THE WORK APPROVED SUBJECT TO A PETITION OF APPEAL SUBMITTED BY JASON CROCKETT AND APPROVED BY MR DAVID MANN, BUILDING CODES ADMINISTRATOR, FOR CITY OF TUCSON DEVELOPMENT SERVICES DEPARTMENT.2.) SUBMIT LETTER OF RESPONSIBILITY, ISSUED BY THE ELECTRICAL CONTRACTOR OF RECORD, STATING THE DATE RESPONSIBILTY FOR THIS PROJECT WAS ASSUMED THANK YOU.
02/21/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*DENIED ISSUES BELOW NOT RESOLVED.
02/12/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0240*THE FOLLOWING ISSUES MUST BE CLARIFIED 1.) THE STATE CONTRACTOR LAW REQUIRED A LICENSED ELECTRICAL CONTRACTOR ON COMMERCIAL PROJECTS. 2.) WIRING EXTENDED TO PATIENT CARE AREAS MUST INSTALLED IN CONDUIT. CONSULT WIHT THE ENGINEER OF RECORD AS TO HOW HE WISHES THIS BE DONE. 3.) THE UNDERSLAB PIPING WAS NOT INSPECTED BY THE ELECTRICAL INSPECTOR. 4.) PLEASE CONTACT MY RAY MAJUTA ELECTRICAL INSPECTOR II AT 791-5550 FOR FURTHER INFORMATION THANK YOU.
02/11/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) ELECTRICAL WIRING IN PATIENT CARE AREAS MUST BE INSTALLED IN METAL CONDUIT OR WITH HEALTH CARE FACILITY MC CABLE WITH HEALTH CARE FACILITY MC CABLE WITH FACTORY MARKINGS. 2.) THE UNDER CONCRETE CONDUIT MUST BE METALLIC CONDUIT APPROVED FOR THE PURPOSE. PVC IS PROHIBITED. SEC ARTICLE 517-B (B) 510-(B)