Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM05356
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/27/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
11/23/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*NOTES 1.) USE LISTED STAPS FOR MC CABLE AND FLEXABLE CONDUIT. 110-3 N.E.C. 2.) SUPPORT MC AND FLEX PER N.E.C. WITHIN 12" OF TERM. |