Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/06/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*COMPETITIVE OK TO CLEAR. |
| 05/03/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 04/30/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NEED TO 1.) GROUND/BOND AIR AND SPRINKLER PIPING (PER NEC 250-84). 2.) LETTER FROM ENGINEER OF RECORD APPROVING TH ELIMINATION OF THE LEIBERT SURGE SUPPRESSORS 3.) LETTER FROM ENGINEER OF RECORD APPROVING DOWN SIZING OF CONDUITS AT TFMRS 1 & 2. 4.) ATTACHMENT OF LABELS FOR A/C UNITS ON ROOF AND ALL TRANS FORMERS, AND ALL SERVICE EQUIPMENT CABINETS. 5.) WIRING OF AIR COMPRESSOR. |