Permit: T01CM05353

Parcel: 14029021B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/06/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*COMPETITIVE OK TO CLEAR.
05/03/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
04/30/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*NEED TO 1.) GROUND/BOND AIR AND SPRINKLER PIPING (PER NEC 250-84). 2.) LETTER FROM ENGINEER OF RECORD APPROVING TH ELIMINATION OF THE LEIBERT SURGE SUPPRESSORS 3.) LETTER FROM ENGINEER OF RECORD APPROVING DOWN SIZING OF CONDUITS AT TFMRS 1 & 2. 4.) ATTACHMENT OF LABELS FOR A/C UNITS ON ROOF AND ALL TRANS FORMERS, AND ALL SERVICE EQUIPMENT CABINETS. 5.) WIRING OF AIR COMPRESSOR.