Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/09/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/08/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) REMOVE RADIANT BARRIER FROM SOUTH SIDE OF FLUE |
| 01/07/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/04/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) CUT RADIANT BARRIER FROM FLUE 2) SUPPORT DUCT WORK IN FRONT LEFT BED 3) REPAIR STOVE DUCT INSTALL |
| 01/03/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEE LAST INSPECTION SHEET |
| 12/31/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1.) BLOCK DUCT BOOT IN FRONT LEFT ROOM 1ST FLOOR. 2.) SUPPORT VENT 90 IN DOWN BATH. 3.) CORRECT OVER NOTCHED STUDS IN LIVING EAST WALL 4.) SHIM WINDOW CRIPPLES 1ST FLOOR REAR WEST WALL & PATIO DOOR TRIMMERS CHECK ALL HEADERS 5.) EQUALIZER DUCT NOT INSTALLED 6.) CORRECT A/C LINE RUN AT REAR GARAGE CEILING 7.) NEED MORE WATER PRESSURE. |
| 12/24/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) FINISH RUNNING GAS PIPE GROUND WIRE 2) CORRECT A/C LINE RUN AT REAR GARAGE CEILING 3) SECURE GAS LINE AT FURNACE PLATFORM IN GARAGE 4) FINISH WIRING FURNACE OUTLET 5) BLOCK DUCT BOOTS 6) STOPPED INSPECTION AFTER GARAGE AND LAUNDRY |