Permit: T01CM05334

Parcel: 136404140

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM05334

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2001 FRAMING Approved IVRS - Inspection 0000*
12/06/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) REMOVE BENT NAILS AT HANGERS 2) MOVE PEX WATER LINE 12" FROM CAN LIGHT AT MASTER BATH 3) A35'S AT 2 X 4 CONNECTION TO GIRDER TRUSS AT MASTER BEDROOM 4) REMOVE BLOCKS BETWEEN TRUSSES AT GIRDER AND CORRECT NAILS
12/05/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) NO PLANS NO PERMIT ON SITE
12/04/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NEED TRUSS SHOP DRAWINGS 2) TRUSS TO GIRDER TRUSS HANGER NAILS ALL BENT OVER, HANGER NAILS ARE BEING SHOT IN WITH A NAIL GUN 3) GARAGE SHEAR NOT TIED TO TRUSSES CANNOT FIND SHEARWALL PAGE THAT RELATES TO SHEAR TRANSFER DETAILS 4) MOVE PEX WATER AWAY FROM REAR BATH CAN LIGHT 5) CANNOT FIND A DETAIL TRUSS TO GIRDER TRUSS HANGER TYPE 6) GAS TEST OK