Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/03/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) NEW SCREW IN SUB-PANEL/DEAD FRONT 2) NEED ALL BREAKERS ON FOR FINAL TEST 3) NEED ALL BREAKERS IN MAIN PANEL MARKED FOR USE 4) NEED BATH VENT FAN COMPLETELY INSTALLED 5) FLEX NO LONGER ALLOWED IN TPR DRAIN (2/01)-MUST BE HARD PIPED WITH UNION 6) TPR TERMINATION NEEDS ELBOW POINTING DOWN 7) WATER HEATER 220 LINE MUST BE SECURED TO WALL 8) PLUMBING VENT ON ROOF MUST BE PAINTED 9) DUCT BOOT REGISTER COVERS MUST BE PRESENT FOR FINAL 10) NON-MASONARY SIDING MATERIALS CANNOT BE IN CONTACT WITH EARTH 11) LADDER MUST BE PROVIDED FOR ACCESS TO ATTIC FOR INSPECTION 12) NEED BACK FLOW PREVENTER ON HOSE BIB 13) SIDING (SOUTHWALL) MUST BE WEATHER TIGHT