Permit: T01CM05327

Parcel: 11201009B


Addresses:

2811 E ALLEN RD


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM05327

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2002 FRAMING Approved IVRS - Inspection 0000*
08/28/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) EXTERIOR WALL 2ND FLOOR BOTTOM PLATE MUST BE NAILED WITH 1-16D AT 12" ON CENTER 2) 2ND FLOOR BATH VENT CUT 3) BLOCK DEFUSER BOOTS 3 SIDES
08/21/2002 FRAMING Denied IVRS - Inspection 0950*/ 1) FIRE BLOCK ALL DOP CEILINGS 2) GAS LINE REQUIRES ELECTRIC BOND 3) ELECTRIC NOT READY 4) PEX NOT ALLOWED WITHIN 12" OF RECESSED LIGHTS 5) FIREPLACE NOT IN 6) BLOCK DEFUSERS 3 SIDES 7) SUPPORT HORIZONTAL DWV AT 4' ON CENTER 8) DUCT KINKED IN CLOSET UPSTAIRS NOTE: GAS AND DWV WET TEST OK TO DRAIN 8) RECALL WHEN ALL TRADES ARE COMPLETE USE INSPECTION CODE 00035 ONLY
08/15/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) FRAME OK BUT CANNOT APPROVE UNTIL ALL TRADES COMPLETE. USE CODE 00035 FOR ALL INTERMEDIATES