Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM05327
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/28/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) EXTERIOR WALL 2ND FLOOR BOTTOM PLATE MUST BE NAILED WITH 1-16D AT 12" ON CENTER 2) 2ND FLOOR BATH VENT CUT 3) BLOCK DEFUSER BOOTS 3 SIDES | |
08/21/2002 | FRAMING | Denied | IVRS - Inspection 0950*/ 1) FIRE BLOCK ALL DOP CEILINGS 2) GAS LINE REQUIRES ELECTRIC BOND 3) ELECTRIC NOT READY 4) PEX NOT ALLOWED WITHIN 12" OF RECESSED LIGHTS 5) FIREPLACE NOT IN 6) BLOCK DEFUSERS 3 SIDES 7) SUPPORT HORIZONTAL DWV AT 4' ON CENTER 8) DUCT KINKED IN CLOSET UPSTAIRS NOTE: GAS AND DWV WET TEST OK TO DRAIN 8) RECALL WHEN ALL TRADES ARE COMPLETE USE INSPECTION CODE 00035 ONLY | |
08/15/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) FRAME OK BUT CANNOT APPROVE UNTIL ALL TRADES COMPLETE. USE CODE 00035 FOR ALL INTERMEDIATES |