Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/01/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/30/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE STRAP AT DRYER VENT FOR NAIL PROTECTION 2) WATER TEST ON DWV REQUIRED 3) FIRE BLOCK AT LAUNDRY WALL 4) SECURE GAS LINE CHECK THRU-OUT 5) CLIP INTERIOR BRG WALL AT LAUNDRY TO GARAGE 6) GROUT TUBS AT DRAIN 7) RAMSET INT BRG WALL 32" ON CENTER 8) ISLAND VENT NOT PER PLAN 9) PROVIDE REVISION FOR ADDITIONAL SINK |