Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/23/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O. |
| 05/20/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MARK DATA PLATES ON AIR HANDLERS W/PROPER HEAT KIT INSTALLED & FUSE DISCONNECT ACCORDINGLY. 2.) CONDENSOR FOR UNIT 1 OVERFUSED. MAX FUSE SIZE IS 20 AMP. RECALL FOR FINAL INSPECTION. |