Inspection Status: Partial Approval
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2001 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
|
| 11/16/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) NO PRESSURE TEST ON PEX. |
| 11/15/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) NO PRESSURE TEST ON PEX PIPE CUT TO WASHER BOX 2.) TRAP ARM FOR WASHER BOX IS NOT TWO PIPE DIAMETERS FROM WEIR OF TRAP TO POINT OF VENT. |