Permit: T01CM05269

Parcel: 117070360


Addresses:

415 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
11/22/2002 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*
08/19/2002 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*1.) NEED PROPER PANEL CLEARANCE. 2.) WILL NEED 22K RATED BREAKERS IN SUB PANELS 1.) NEED R CLIPS IN EVERY FUSE. 2.) HAVE ENGINEER PROVIDE CIRCUIT PHASING BLOCK AND RED USED THROUGHT SINGLE PHASE THIS SHOULD BE BALANCED. 3.) PLAN CALLS FOR 3 POLE DISCONNECTS AT SERVICE 4.) GROUNDING BUSHING AND BONDINGS JUMPERS THROUGH OUT SERVICE IN CLUDES RISER (2).
05/29/2002 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0920*DENIED NO ANSWER NO ACCESS PLEASE RECALL.