Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/22/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000* |
| 08/19/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*1.) NEED PROPER PANEL CLEARANCE. 2.) WILL NEED 22K RATED BREAKERS IN SUB PANELS 1.) NEED R CLIPS IN EVERY FUSE. 2.) HAVE ENGINEER PROVIDE CIRCUIT PHASING BLOCK AND RED USED THROUGHT SINGLE PHASE THIS SHOULD BE BALANCED. 3.) PLAN CALLS FOR 3 POLE DISCONNECTS AT SERVICE 4.) GROUNDING BUSHING AND BONDINGS JUMPERS THROUGH OUT SERVICE IN CLUDES RISER (2). |
| 05/29/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0920*DENIED NO ANSWER NO ACCESS PLEASE RECALL. |