Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T01CM05269
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2002 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection 0000* | |
08/19/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0999*1.) NEED PROPER PANEL CLEARANCE. 2.) WILL NEED 22K RATED BREAKERS IN SUB PANELS 1.) NEED R CLIPS IN EVERY FUSE. 2.) HAVE ENGINEER PROVIDE CIRCUIT PHASING BLOCK AND RED USED THROUGHT SINGLE PHASE THIS SHOULD BE BALANCED. 3.) PLAN CALLS FOR 3 POLE DISCONNECTS AT SERVICE 4.) GROUNDING BUSHING AND BONDINGS JUMPERS THROUGH OUT SERVICE IN CLUDES RISER (2). | |
05/29/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0920*DENIED NO ANSWER NO ACCESS PLEASE RECALL. |