Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM05269
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
09/17/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NEED CITY APPROVED REVISION RECALL INSPECTION. | |
05/22/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) UNDERGROUND LATERAL TO NEW SERVICE APPROVED ONLY 2.) INTERMEDIATE 3.) WILL NEED ENGINEER APPROVED STAMPED LETTER. A.) PANEL BOARD LOCATION CHARGED TO IN CLOSET. B. PLANS CALLS FOR BOLT ON BREAKER C. CANNOT USE OLD PANEL BOARD AS JUNCTION BOX. MUST HAVE AN APPROVED JUNCTION BOX. 4.) PANEL BOARD MUST CONTAIN THE MINIMUM CIRCUIT CAPABILITY AS WHAT IS ON PLAN. 5. LABEL ALL PANEL AND DISCONNECTS. 6.) NEED MIN CLEARANCE PER 110-26. 7.) PROVIDE ENGINEER DERATING CALCULATION AN COMBINING A/C FEEDER CIRCUITS. 8.) COPPER BELOW DISCONNECTS NOT APPROVED. |