Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/07/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) CORRECTIONS MADE OK ABS WATER TEST OK PEX PRESSURE TEST OK 2.) CLOSET FLANGES OK 3.) TUBS OK 4.) OK TO COVER ALL AREAS. |
| 06/04/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) SEE 313.2. ITEM NUMBER 2 SEPARATION OF HOT & COLD WATER DISTRIBUTION PIPING HOT & COLD WATER PIPING MAY NOT BE BUNDLED TOGETHER. 2.) CONTRACTOR TO PAY REINSPECTION FEE. |
| 06/03/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE INSTALLATION STANDARD ALLOWING PEX PIPING TO BE BUNDLED TOGETHER. 2.) DO NOT COVER UNTIL THIS ISSUE IS RESOLVED. |
| 05/31/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
BOTH GAS LOCKED NO ACCESS. |
| 05/30/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1.) GAS PIPING OK PRESSURE TEST OK 2.) ABS NEEDS WATER TEST THROUGH ROOF. |
| 05/22/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) PROVIDE DOCUMEUTATION FOR COMPLETION OF HCS CONNECTION 2.) SEE NOTE #3 1/7/02 WHY WASNT I CALLED FOR A PRE-POUR INSPECTION? |