Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM05263
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) CORRECTIONS MADE OK 2.) ABS WATER TEST OK PEX PRESSURE TEST OK 3.) CLOSETT FLANGES OK 3.) TUBS OK 4.) OK TO COVER ALL AREAS. | |
06/04/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) WATER ALL OVERFLOOR, WATER TEST , MAYBE A LEAK? 2.) SEE 313.2 NUMBER 2 INTERPRETATION MANUAL. BUNDLING OF HOT & COLD WATER PIPING. 3.) CONTRACTOR TO PAY RE-INSPECTION FEE. | |
06/03/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PROVIDE INSTALLATION STANDARD FOR BUNDLING OF PEX PIPE. 2.) DO NOT COVER UNTIL THIS ISSUE HAS BEEN RESOLVED. | |
05/31/2002 | PLUMBING - INTERMEDIATE | Denied | BOTH GATES LOCKED NO ACCESS. | |
05/30/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) GAS PIPING OK PRESSURE TEST OK 2.) NEED TO SEE ABS WATER TEST THROUGH ROOF. | |
05/22/2002 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*1.) SEE NOTE #3 1/7/02 WHY WASNT I CALLED FOR A PREPOUR INSPECTION 2.) INTERMEDIATE REQUIRES CORRECTIONS REVIEWED W/PLUMBER. |