Permit: T01CM05263

Parcel: 117144370


Addresses:

759 S 9TH AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM05263

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/07/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) CORRECTIONS MADE OK 2.) ABS WATER TEST OK PEX PRESSURE TEST OK 3.) CLOSETT FLANGES OK 3.) TUBS OK 4.) OK TO COVER ALL AREAS.
06/04/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) WATER ALL OVERFLOOR, WATER TEST , MAYBE A LEAK? 2.) SEE 313.2 NUMBER 2 INTERPRETATION MANUAL. BUNDLING OF HOT & COLD WATER PIPING. 3.) CONTRACTOR TO PAY RE-INSPECTION FEE.
06/03/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) PROVIDE INSTALLATION STANDARD FOR BUNDLING OF PEX PIPE. 2.) DO NOT COVER UNTIL THIS ISSUE HAS BEEN RESOLVED.
05/31/2002 PLUMBING - INTERMEDIATE Denied BOTH GATES LOCKED NO ACCESS.
05/30/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999* 1.) GAS PIPING OK PRESSURE TEST OK 2.) NEED TO SEE ABS WATER TEST THROUGH ROOF.
05/22/2002 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*1.) SEE NOTE #3 1/7/02 WHY WASNT I CALLED FOR A PREPOUR INSPECTION 2.) INTERMEDIATE REQUIRES CORRECTIONS REVIEWED W/PLUMBER.