Permit: T01CM05260

Parcel: 117144350


Addresses:

775 S 9TH AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM05260

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/07/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) CORRECTIONS MADE OK ABS WATER TEST OK PEX PRESSURE TEST OK 2.) CLOSET FLANGES OK 3.) TUBS OK 4.) OK TO COVER ALL AREAS.
06/04/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) SEE 313.2 ITEM NUMBER TWO INTERPETATION MANUAL BUNDLING OF HOT AND COLD WATER PIPING. 2.) CONTRACTOR TO PAY RE-INSPECTION FEE.
06/03/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.0 PROVIDE LISTING FOR BUNDLING OF PEX PIPE. 2.) DO NOT COVER UNIT THIS HAS BEEN RESOLVED.
05/31/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*BOTH GAS LOCKED NO ACCESS.
05/22/2002 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*1.) SEE NOTE # 01/07/02. WHY WASN'T I CALLED FOR PRE POUR INSPECTION? WHATEVER I WANTED TO SEE, IS NOW UNDER CONCRETE; ANY SUGGESTIONS? 2.) PROVIDE LISTING AND INSTALLATION INSTURCTIONS FOR AIR ADMITTANCE VALVE ONLY ACCEPTED WHEN STRUCTURAL CONDITIONS LIMIT ANY OTHER INSTALLATION. 3.) PROVIDE LISTING FOR "BUNDILNG " OF PEX PIPE.