Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM05257
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PARTITION WALLS ARE ROUGHED IN OK CENTER OFFICE. | |
10/31/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) THERE IS A ) MISSING BETWEEN CONF. ROOM & ROOM 105 (IN NEW WALL EXTENSION.) 2.) USE STEEL "BANG PLATES OVER STUDS WHERE THE DISTANCE FROM THE FACE OF THE STUD TO THE MC CABLE AND OR ALUM. FLEX IS LESS THAN 1 1/4." BE ADVISED: ALL NEW, ADDED, OR RELOCATED LAY-IN OR RECESSED LIGHT FIXTURES INSTALLED IN THE SUSPENTED CIELING MUST BE FITTED WITH TWO (2) SEISMIC WIRES AND THE EXTENSION OF ALL "EARTHQUAKE" CLIPS (4), OR SCREWED TO THE GRID AT EACH END (1 SCREW AT EACH END.) THANK. |