Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/11/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST OK 2.) WATER DISTRIBUTION IS OK 3.) P.O.C. OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK 4.) OK FOR DRYWALL. |
| 12/06/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) MUST HAVE A MIN OF 2" WASTE FOR 2 FIXTURE UNIT FIXTURE. 2.) MUST PROVIDE WATER TEST ON WASTE & VENT ALL THE WAY TO ROOF. 3.) NO APPROVED PLDG. DRAWING ON SITE. |