Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05249
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
01/07/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*9AM NOT READY MECH CONTRACTOR NOT ON SITE YET. | |
01/04/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) ROOF A.) SUPPORT SEALTITE B.) LOOSE SEALTITE FITTINGS. C.) RECEPTACLE TO BE WEATHER PROOF WHEN PLUGED IN D.) CAN NOT TAP FROM 3 O FOR RECEPTACLE E.) LABEL DICONNECTS. F.) EXHAUST HOOD TO HAVE COVER OVER EXPOSED CONDUCTORS G.) PLEASE TERMNATE GROUND WITH APPROVED CONNECTOR. H.) PROTECT SEALTITE WHERE PASSING THRU METAL 2.) USE APPROVED SUPPORT METHODS FOR SECURING CONDUIT. THAN IS NOT APPROVED. |