Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/07/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 12/31/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) SUPPORT M/C CABLE AS PER CODES 334 & 300-11 WITHIN 12" OF BOX AND INDEPENDANTLY OF CEILING WIRE 2.) PLEASE ATTACH FIXTURES TO GRID. 3.) STRAP CONDUIT ABOVE WASH AREA. SUPPORT IS IN BUT NOT TIED OFF OK TO CLEAR POWER FOR TESTING SUBJECT TO OTHER INSPECTION. HAVE A HAPPY NEW YEAR. |