Permit: T01CM05150

Parcel: 128140620


Addresses:

5238 E 18TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/07/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) FINAL SUBJECT TO COMPLETION OF ELECTRICAL SERVICE CHANGE OUT FROM NEW LOCATION.
01/29/2002 ELECTRIC - FINAL Denied 1.) REPLACE ALL OPEN BULB FIXTURES IN CLOSETS WITH FIXTURES WITH GLASS COVER OVER BULB. 2.) ADD TWO GROUND RODS TO THE ELECTRICAL SERVICE. PRESENT GROUNDING IS INADEQUATE. 3.) REMOVE WATER PVC PIPE AND INSTALL SCHEDULE 80 PVC.USE PROPER TERMINATING FITTINGS. THIS IN REFERENCE TO PVC PIPE FROM MAIN PANEL TO? 4.) REPLACE ANY CIRCUIT BREAKERS IN THE PANELS THAT ARE NOT OF THE PANEL MANUFACTURERS BRAND. 5.) COMPLETE THE CIRCUIT INDEX. 6.) COMPLETE ALL WORK OF ELECTRICAL FINISH TO COMPLETION.