Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/03/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) TWO WAY C.O. TO GRADE IS OK 4.) OK FOR BACKFILL. 5.) NOTE: WASHER BOX DRAIN WILL REQUIRE A C.O. IN WALL. |