Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM05114
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2001 | MECHANICAL - FINAL | Approved | ||
11/19/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*PROVIDE COVERS OVER CANVAS CONNECTORS ON ROOF. 2.) PROVIDE OUTSIDE AIR VENTS AS PR PLANS 3.) #10 WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT. 4.) MARK UNIT DATA PLATE FOR PROPER HEAT STRIP INSTALLED & FUSE UNIT ACCORDINGLY. 5.) LABEL EQUIPMENT PERMANENTLY W/SUITE NUMBER OR ADDRESS. 6.) CONDENSATE TERMINATION NOT TO PLAN. |