Permit: T01CM05114

Parcel: 130140260


Addresses:

4066 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/20/2001 MECHANICAL - FINAL Approved
11/19/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*PROVIDE COVERS OVER CANVAS CONNECTORS ON ROOF. 2.) PROVIDE OUTSIDE AIR VENTS AS PR PLANS 3.) #10 WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT. 4.) MARK UNIT DATA PLATE FOR PROPER HEAT STRIP INSTALLED & FUSE UNIT ACCORDINGLY. 5.) LABEL EQUIPMENT PERMANENTLY W/SUITE NUMBER OR ADDRESS. 6.) CONDENSATE TERMINATION NOT TO PLAN.