Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2001 |
MECHANICAL - FINAL |
|
Approved |
|
| 11/19/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*PROVIDE COVERS OVER CANVAS CONNECTORS ON ROOF. 2.) PROVIDE OUTSIDE AIR VENTS AS PR PLANS 3.) #10 WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT. 4.) MARK UNIT DATA PLATE FOR PROPER HEAT STRIP INSTALLED & FUSE UNIT ACCORDINGLY. 5.) LABEL EQUIPMENT PERMANENTLY W/SUITE NUMBER OR ADDRESS. 6.) CONDENSATE TERMINATION NOT TO PLAN. |