Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2001 |
MECHANICAL - FINAL |
|
Approved |
|
| 11/19/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*PROVIDE COVERS OVER CANVAS CONNECTORS ON ROOF. 2.) PROVIDE OUTSIDE AIR VENTS AS PR PLANS 3.) #10 WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT. 4.) MARK UNIT DATA PLATE FOR PROPER HEAT STRIP INSTALLED & FUSE UNIT ACCORDINGLY. 5.) LABEL EQUIPMENT PERMANENTLY W/SUITE NUMBER OR ADDRESS. 6.) CONDENSATE TERMINATION NOT TO PLAN. |