410 E 7TH ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM05102

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*TEST OK ON EXISTING GAS LINE 1= WATER HEATER ONLY NO OTHER FIXTURES CALL GAS CO 889-1888.
10/12/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*1.) PLEASE PROVIDE A 10LBS PRESSURE ON COMPLETE SYSTEM 2.) HAVE YOUR PLUMBER PROVIDE APPROVED TYPE VENT 1" CLEARANCE FOR DOUBLE WALL & 6 FOR SINGLE WALL AT WATER HEATER PROVIDE DOUBLE WALL 90 AT WALL. 3.) RELIEF LINE TO OUT SIDE BLDG. 4.) HAD PIPE THROU WALL AT WATER HEATER THEN FLEX.