Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM05094

Parcel: 11306129E

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/22/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000* FIRE DAMPER PENETRATION DUCTS AND RETAINING ANGLES LOOK GOOD FINALLY.
03/19/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999* PROVIDE ACCESS TO INSIDE OF FIRE DAMPER LAST END OF HALLWAY. ANGLE IRON ON FIRE DAMPERS MUST COVER THE CORNERS OF OPENING. IF YOU ARE GOING TO HAVE MOVICES INSTALLING FIRE DAMPERS THEY NEED TO KNOW WHAT THEY ARE DOING.
03/18/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) COMPLETE RETAINING ANGLES ON TOP, BOTTOM AND SIDES ON BOTH SIDES OF WALL ON BOTH SIDES OF WALL ON ALL FIRE DAMPERS. THESE NEED TO BE TIGHT AGAINST WALL AND SEALED TIGHT. 2.) FUME HOODS PROGRESSING NO FINISHED. 3.) SHEET ROCK NEEDS TO BE ON BOTH SIDES OF RATED WALL. THIS INCLUDED REAR OF GAS LINE.
03/08/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*NEED TO SEE FIRE DAMPER OPENINGS PROVIDE AN ACCESS DOOR FOR FIRE DAMPER ON EAST END OF HALLWAY. INSULATE CONDENSATE DRAIN LINE ABOVE CEILING.