Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/14/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 05/08/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*LETTER FROM ENGINEER NEED TO BE MORE SPECIFIC FOR CERTIFICATION PLEASE CORRECT AND RESUBMIT. |
| 04/12/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
1.) METER HEATER NOT INSTALLED AT THIS TIME. 2.) FUME HOOD NEED TO BE FIELD LABEL BY A THIRD PARTY AGENCY. 3. MAIN DISCONNECT IS MISSING DOOR RELEASE HARD WARE 4.) A/C DISCONNECT TO BE LABELED. |
| 04/05/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE USE APPROVED M/C CONNECTIONS TO BOXES 2. WE NEED TO SUPPORT THE PVC STUBED UP INTO THE CABINET 3. FINISH INSTALLATION MOTOR STARTER FOR THE COMPRESSOR ALSO MAINTAIN WORKING CLEARENCE ALSO CHECK HEATERS. 4.) GROUNDING CONDUCTOR TO BE IDENTIFIED ITS ENTIRE LENGTH 250-119. 5.) PLEASE MAINTAIN COLOR PHASING 6.) PLEASE VERIFY LISTING AND LABELING OF FUME HOOD 7.) VERIFY DERATING OF CONDUCTORS 310-15. AND NOTE 5 ON PLANS 8.) M/C CABLE TO BE STRAPED AS PER CODE WITHIN 12" OF BOXES 9.) MAIN DISCONNECT: 1 NEED R CLIPS. 2.) LUGS FOR GROUNDS CAN NOT BE STACKED. C.) WHERE IS THE HARDWARE FOR DOOR RELEASE? |