Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/06/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 12/05/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE STRAPS AT OVER NOTCHED OR BORED HOLES AT DOUBLE TOP PLATE AT GARAGE 2) NAIL PROTECTION FOR PLUMBING AND ELECTRIC, CHECK THRU-OUT 3) REMOVE SCREEN AT DRYER VENT T-TOP 4) SECURE ROMEX CHECK THRU-OUT 5) STRAP AT RANGE HOOD VENT 6) COMPLETE GAS LINE AT FIREPLACE |
| 12/04/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED TO COMPLETE TRADES |