Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM05054

Parcel: 113030060


Addresses:

906 E ROGER RD #02

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/22/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
03/19/2002 BUILDING - FINAL Denied IVRS - Inspection 0920*/ 1) NO ACCESS, 8:15 AM
03/12/2002 BUILDING - FINAL Denied IVRS - Inspection 0950*/ 1) OUTSIDE ELECTRIC OUTLETS CANNOT BE ON KITCHEN GFCI CIRCUIT 2) KITCHEN COUNTER GFCI OUTLETS MUST BE ON 2 EACH 20 AMP SEPARATE CIRCUITS 3) MAXIMUM ALLOWED FLEX GAS CONNECTOR ON WATER HEATER 36" 4) STOOP REQUIRED AT SLIDING GLASS DOORS-36" DEEP BY DOOR WIDTH 5) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 6) BEDROOMS HAVE NO HEAT. REVISE PLANS FOR ADDED REQUIRED HEAT 7) POST ADDRESS 906 #2 ON UNIT VISABLE FROM STREET