Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM05042
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/05/2002 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) FROM LAST INSPECTION NEED A LADDER TO GET INTO ATTIC SPACE 2) POST TO BEAM CONNECTIONS TOP AND BOTTOM FINISH NAILING HARDWARE. NO PLAN TO CHECK REQUIRED CONNECTION, COULDN'T FIND IN SIMPSON BOOK ANY POST TO BEAM CONNECTOR USING 8D NAILS USE CORRECT NAILS CHECK PLAN 3) NEED A LETTER FROM GALE INSULATION STATING THAT ALL INSULATION WAS REMOVED FROM ON AND AROUND FIREPLACE | |
| 01/29/2002 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) LEVEL A.C. UNIT PUT IT ON SKIDS, SECURE FLEX CONDUIT GET IT UP OFF THE ROOF DECK 2) MISSING FIREPLACE FLUE AND CAP, CHASE CAP FIREPLACE CHASE IS FULL OF INSULATION 3) NEED A NON COMBUSTIBLE HEARTH AT FIREPLACE 4) NEED A STEP LADDER TO GET INTO ATTIC 5) FINISH POST TO BEAM AND BOTTOM POST HARDWARE 6) INSUALTION WILL HAVE TO BE REMOVED FROM FIREPLACE CHASE AND FROM FIREPLACE UNIT 7) NEED ALL CERTIFICATES 8) NEED HOUSE ADDRESS NUMBER |