Permit: T01CM05014

Parcel: 14021001B


Addresses:

5301 S PARK AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/08/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/02/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) CIR A 34 + 36 FREEZER IMPROPER CONNECTIONS AT J-BOX COVER MISSING, BOX NOT GROUNDING & ALL OTHER ELECTRICAL BOXES MISSING COVERS. EXTRA CIRCUIT PULLED, UNDERGROUND NOT INSPECTED ALL ROMEX TO BE IN APPROVED RACE WAY AS PER PLAN. 2.) BOND SAW AT PNL A 60 AMP 2 POLE, PANEL SHOWS COPPER NOT ALUM ALUM GOOD ONLY FOR 50 AMPS RECEPTACLE RATED 125V 30 AMPS 3.) PANEL A NOT SCHEDULE. 4.) ROOF HAS 2 AC UNITS ON, NOT ON PLAN CANNOT BE RUN IN PVC, REMOVE UN USED WIRING, CORRECT WIRING TO UNITS ON ROOF, EX FAN & COOLER WIRED INCORRECTLY. 5.) CONDUIT FROM PNL A TO REFRIGERATION UNITS CONTAINING B-1,B-3,B-5,B-7, B-6-8 RUN IN CONDUIT WITH PVC FITTING AT END NEEDS A J-BOX TO FEED FLEX. 6.) THERE IS NO NEW PANEL B AND NOT WIRED AS PER PLAN 7.) SERVICE NEEDS TO BE CLEANED UP. THIS JOB NEEDS TO BE INSTALLED AS PER PLAN. 8.) ADDRESS WIRING METHODS IN SODA FREEZER TO BE CORRECTED. 9.) CHECK ALL FREEZER UNITS CONNECTUINS & EXPOSE FOR INSPECTION 10.) OWNER TO CHECK ALL EQUIMENT FOR PROPER LISTING AND PROVIDE.