Permit: T01CM05008

Parcel: 112073510


Addresses:

2842 E SYLVIA ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/31/2003 FRAMING Approved IVRS - Inspection 0000*
03/24/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) SOME ADDITIONAL ELECTRIC OUTLETS ARE REQUIRED (EVERY WALL 2' OR WIDER AND EVER 12' AROUND ROOM) 2) ROMEX MUST BE STAPLED WITHIN 6" OF BOXES 3) MAKE UP GROUNDS IN BOXES 4) NAIL PROTECT ROMEX OF PLUMBING PENETRATIONS LESS THAN 1 1/4" FROM FACE OF FRAMING 5) FINISH FRAMING AT FRONT WINDOW 6) SUPPORT LOOSE END OF 4 GANG ELECTRIC BOXES
09/30/2002 FRAMING Denied IVRS - Inspection 0999* COMPLETE ALL TRADES