Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/11/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/10/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 03/29/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935* |
| 02/14/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999$/ 1) REFRIGERATOR SHOULD NOT BE ON GFCI PROTECTED OUTLET 2) RANGE HOOD NOT IN BAR WIRES 3) SOUTH OUTSIDE OUTLET LOOSE 4) REMOVE WIRES FROM NORTHWEST ROOM TO BE DEMOLISHED 5) 3 WIRE RANGE OUTLET NOT ALLOWED-4 PRONG PLUG REQUIRED 6) STOPPED INSPECTION 7) HOUSE MUST BE COMPLETE AND READY TO OCCUPY FOR FINAL INSPECTIONS NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE |
| 01/30/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SOUTH UNIT NOT READY 2) CANNOT APPROVE ANY FINAL INSEPCTION ITEMS UNTIL UNIT IS COMPLETE AND READY TO OCCUPY 3) RANGE HOOD, COUNTERS AND SINKS NOT IN |
| 01/18/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |