Inspection History: MECHANICAL - HOODS
Permit Number - T01CM04972
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2002 | MECHANICAL - HOODS | Approved | IVRS - Inspection 0000* | |
| 01/09/2002 | MECHANICAL - HOODS | Denied | IVRS - Inspection 0999*1.) NEED TO SEE LISTING ON BANDING & CLAMPING MATERIAL. MUST BE LISTED FOR USE ON FIRE WRAP. 2.) WRAP WAS NOT INSTALLED PER INSTRUCTIONS FILAMENT TAPE IS MISSING. 3.) WRAP ON GREASE DUCT IN ATTIC DOES NOT HAVE MIN. 3" OVERLAP ON JOINTS 4.) BANDING HAS CUT THROUGH OUTER LAYER OF WRAP. 5.) STRAP UP FLEX DUCT OFF OF GRID & LIGHTS. 6.) REPAIR CONDENSATE DRAINS ON ROOF 7.) COVER CANVAS CONNECTOR ON AC UNIT, PROVIDE SCREEN AROUND CONDENSOR FAN BLADE, PROVIDE CONDENSATE DRAINS. REMOVE ABANDONED EQUIPMENT FROM ROOF. 8.) PROVIDE OUTSIDE AIR VENTS ON AC UNITS. 9.) STAT WIRE EXPOSED TO SUNLIGHT. |