Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T01CM04932

Parcel: 136242870


Addresses:

7021 E BROOKS DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/28/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/13/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK ON ALL ITEMS ABOVE EXCEPT POWER CHECK 2) WILL CHECK ALLOUTLETS ATER POWER IS TURNED ON
10/09/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/08/2001 ELECTRIC - FINAL Not ready for Inspection