Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM04932
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000*ALL FINALS OK ON BOTH PERMIT. | |
10/09/2001 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SAME AS LAST INSPECTION | |
10/08/2001 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NEED POWER TURNED ON FOR POWER CHECK 2) REAR PORCH FRAMING POST AT CONCRETE NOT PER CODE NEED CONNECTION TO HOLD DEVICE, RAFTER TO FACIA CONNECTION NOT APPORVED, BEARING RAFTER TIED TO FACIA WITH JOIST HANGER 3) MATERIAL USED TO COVER CEILING MUST BE APPROVED, WHAT IS IT? 4) GARAGE ENCLOSURE NOT ON PERMIT DESCRIPTION 5) YOU NEED TO CLEAR UP ALL WIRING IN GARAGE, STORE ROOM EXPOSED ROMEX, UNLISTED CONDUIT AND CONNECTIONS 6) RANGE OUTLET NOT SECURED 7) YOU NEED TO HAVE YOUR POWER TURNED ON 8) BANG BOARD HEATER TO BE ON IT'S OWN CIRCUIT (12 AMP UNIT) IT'S OVER LOADING THE LIGHTING CIRCUIT 9) YOU NEED A PLAN SHOWING A CROSS SKETCH OF REAR ADDITION 10) MAIN DOOR HOUSE TO GARAGE TO BE SOLID CORE SELF CLOSING |