Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM04926

Parcel: 105095510


Addresses:

4701 N STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM04926

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*1000 WATT LIGHTS IN PARKING LOT REMOVED IF REINSTALLED A PERMIT IS REQUIRED.
10/29/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) 1000 WATT LIGHT FIXTURE TO MEET LIGHTING CODES. 2.) SUPPORT WIRES TO BE INSTALLED FOR ALL FIXTURES & EXIT SIGNS 1 PER 4' OF FIXTURE (ENTRY) & EXIT. 3.) VERIFY INTER LOCK FOR VENTILATION IN TIRE SHOP. 4.) TIGHTEN LOCK NUTS IN GENERAL CABINETS. 5.) PLEASE VERIFY LISTING LABEL FOR TRANSFER SWITCH. 6.) NEED REJECTION PINS FOR 600 AMP SWITCH AND LABEL. 7.) FINISH ROOF AS PER INSPECTION DATED 9/26/02. 8.) PARKING LOT LIGHT TO HAVE APPROVED AND STAMPED PLAN FOR INSPECTION ALSO APPROVED LIGTH FIXTURES.
10/28/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*HOLD FOR RH TO BE INSPECTED
10/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*SAME AS 10/22/02 CALLED CONTRACTOR ASKED FOR RICK HOLLAND TO MAKE FINAL INSPECTION HE IS FAMILAR WITH JOB RAY MAJUTA.
10/22/2002 ELECTRIC - FINAL Denied UNABLE TO LOCATE ANY PEOPLE WITH KNOWLEDGE OF WORK LOCATIONS IF CONTRACTOR RECALLS FOR INFORMATION PLEASE HAVE HIM SET UP A MEETING WITH INSPECTOR FOR INSPECTION.
09/26/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) MAINTAIN WORKING CLEARENCES IN OF A/C GAS PACKS ON ROOF. 2.) PROTECT FEEDER CONDUCTOR TO BREAKER 3.) PLEASE HAVE EXHAUST FANS OPEN FOR INSPECTION. OK TIRE SHOP & WEARHOUSE FOR C OF O SUBJECT TO OTHER INSPECTORS OK FRONT EXTERIOR WALLS.
09/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) OK TO PACK SEAL OFF FOR INSPECTION. 2.) RECEPTACLES IN TIRE SHOP TO BE GFI 511-3.) IS EXHAUST FAN TO BE INTER LOCKED? 4.) MAINTAIN DISCONNECTING MEANS PER TAP POLES 240. 5.) CAN NOT USE SHEET METAL SCREWS PER GROUNDING 250-8.
6.) GROUND JUNCTION BOXES 250-148. 7.)
WE HAVE LOOSE CONDUIT FITTING UNDER COUNTER CHECK ROOF & TIRE WAREHOUSE NEXT INSPECTION
09/09/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) WE HAVE LOOSE FITTING AT ICE MACHINE FLEX 2.) ECCENTRICS AT 200AMP DISCONNECT PULLING OUT PLEASE USE APPROPRIATE SIZED WASHER TO CORRECT. 3.) PLEASE MOVE FLEX CONDUIT OUT OF TRIP HAZARD AREA IN FRONT OF SERVICE. 4.) GUTTER IS OVERFILLED AS PER CODE. 5.) FINISH BATHROOM AT TIRE SHOP. OK TEMP C OF O
07/17/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK PHARMACY, PHOTO,VISION CARE, FOR FINAL.
07/09/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1.) SUPPORT M/C CABLE AS PER CODE ABOVE CEILING 2.) A SUPPORT WIRE ARE NEEDED FOR CANS. 3.) USE APPROVED FITTINGS FOR M/C CABLE AND TIGHTEN FITTINGS 4.) LABEL DISCONNECTS IN COOLERS 5.) BONDING BUSHINGS AT CONCENTRISS OF 277/480 DISCONNECT 250-97. OK SMOKER LOUNGE.
07/08/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
07/03/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) FIXTURE TO BE ATTACHED TO GRID 410-16 CITY AMENDMENTS. 2.) WE CAN NOT HAVE CORDS PLUGED IN ABOVE GRID 400-7,400-8. 3.) PLEASE LABEL TRANSFORMER & DISCONNECTS. 4.) SUPPORT M/C WITHIN 12' OF CANS.
07/01/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) TIGHTEN FITTINGS FOR WATER HEATER AND SUPPORT FLEX CONDUIT 2.) SUPPORT M/C CABLE AND TIGHTEN FITTINGS 3.) SUPPORT FLEX UNDER COUNTERS 4.) PLEASE OPEN GRID CEILINGS FOR INSPECTIONS. 5.) NEED TO SEE LETTERS AUTURIZING USAGES AS PREVIOUS REQUESTED. 6.) PLEASE HAVE ELECTRICTIAN PRESENT TO OPEN AND ACCESS ELECTRICAL EQUIPMENT LIGHTS AND TRANSFORMER AND PANELS. 7.) MAINTAIN WORKING CLEARENCE IN FRONT OF PANEL "LPH". 8.) WATER HEATER NOT TO BE CORD CONNECTED. 9.) PLEASE PROVIDE A STEP LADDER FOR ACCESSES.