Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/31/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 09/04/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) FINISH GROUNDS AT JUNCTION BOXES. 2.) VERIFY WIRE FILL IN GUTTER 362 & 374. 52 CURRENT CARING CONDUCTORS IN A 8 X 8 X 48 GUTTER. PLEASE LEAVE OPEN A COUPLE OF TILE FOR INSPECTION LATER. |
| 09/03/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*SUPPORT ALL CONDUITS WITHIN 3' OF GUTTER 2.) PLEASE VERIFY WIRE FILL FOR GUTTER. 3.) FIXTURES TO BE ATTACHED TO GRID 4.) SUPPORT M/C CABLE AS PER CODE EVERY 6' ALSO AS PER 300-11 AT BOTH ENDS. 5.) GROUNDS ARE NEEDED AT JUNCTION BOXES 250-148. 6.) WE HAVE OPEN JUNCTION BOXES. 7.) PLEASE TIGHTEN M/C FITTINGS. |