Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM04926
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
09/04/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) FINISH GROUNDS AT JUNCTION BOXES. 2.) VERIFY WIRE FILL IN GUTTER 362 & 374. 52 CURRENT CARING CONDUCTORS IN A 8 X 8 X 48 GUTTER. PLEASE LEAVE OPEN A COUPLE OF TILE FOR INSPECTION LATER. | |
09/03/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*SUPPORT ALL CONDUITS WITHIN 3' OF GUTTER 2.) PLEASE VERIFY WIRE FILL FOR GUTTER. 3.) FIXTURES TO BE ATTACHED TO GRID 4.) SUPPORT M/C CABLE AS PER CODE EVERY 6' ALSO AS PER 300-11 AT BOTH ENDS. 5.) GROUNDS ARE NEEDED AT JUNCTION BOXES 250-148. 6.) WE HAVE OPEN JUNCTION BOXES. 7.) PLEASE TIGHTEN M/C FITTINGS. |