Permit: T01CM04914

Parcel: 107132770


Addresses:

2642 N LOS ALTOS AV

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
02/20/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*OK TO CLEAR CABLE DROPS UNITS 1-4.
02/12/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*THE 2 1/2 RISER HAS TO HAVE A GROUND BUSHING WITH A #4 BARE COPPER TO ENCLOSURE, SINCE THE UNPROTECTED CONDUCTORS ENTER THUR A CONCENTRIC KO 250-94 OF NEC REQUIRES A GROUND BUSHING NOT PLASTIC.
02/08/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*