Permit: T01CM04897

Parcel: 11204370E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/24/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
10/16/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*OK FOR CEILING TILES. 1.) STILL NEED TO SEE FINAL CONDENSATE DRAIN CONNECTION TO LAV. 2.) PAINT EXPOSED PVC W/LATEX PAINT. 3.) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT TO AC UNITS. 4.) PROVIDE OUTSIDE AIR VENTS. 5.) PROVIDE A CAP ON WATER HEATER VENT.