Permit: T01CM04897

Parcel: 11204370E

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/13/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) PLBG FINAL IS OK
2.) OK FOR C OF O.
10/28/2002 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*OK FOR TEMP C OF O AS PER STEVE LONG. ONLY.
10/25/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST STRAP GAS LINE IN WATER HTR RM 2.) MUST SECURE EXPANSION TANK @ WATER HTR. 3.) MUST PROVIDE VACCUM BREAKER @ NORTH HOSE BIB. 4.) P-TRAP ON SHAMPOO SINK IS CANTED. 5.) MUST INSTALL DRYER OR CAP OFF GAS VALVE. 6.) MUST PERM CAP WASTE IN WALL FOR LAUNDRY SINK. 7.) MUST ANCHOR BACKFLOW PREVENTERS @ FONT SPA. 8.) CENTER SHAMPOO SINK REQUIRE VACCUM BREAKER 9.) MUST TEST & CERIFY BACKFLOW PREVENTERS FOR FOOT SPA. 10.) SI INTERCEPTOR REQUIRES ACCESS OR PIT.
10/24/2002 PLUMBING - FINAL Not ready for Inspection PLEASE INSTALL ALL FIXTURE BEFORE CALLING FOR INSP. FOOT SPA WILL REQUIRE BACKFLOW DEVICE.