Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/25/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/27/2002 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) WASTE & VENT SYSTEM IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) GAS PRESSURE TEST IS OK 4.) OK FOR DRYWALL UPON BLDG. INSPECTOR APPROVAL. |
| 08/23/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) MUST STRAP DOWN ALL COPPER DROP IN WALL 2.) HORIZONTAL VENTS MUST BE STRAPPED EVERY 4' 3.) OUTLET FOR SOLID INTERCEPTOR HAS OSTRUCTION OF FLOW @ OUTLET DUE TO BUSHING SEE SECTION 311.5 94 UPC. 4.) WOOD SHIMS ARE NOT APPROVED MATERIAL FOR SECURING COPPER. MUST USE APPROVED STRAPS. 5.) EXTERIOR ABS WASTE LINES MUST HAVE A MIN. 12" OF COVER FROM SUB GRADE. 4.) MUST TEST WASTE & VENT SYSTEM ALL THE WAY TO TOP OF VENT THRU ROOF. SEE SECTION 712.2 94 UPC 5.) GAS SYSTEM NOT TO APPROVED PLAN. |