Permit: T01CM04897

Parcel: 11204370E

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/25/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
08/27/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) WASTE & VENT SYSTEM IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) GAS PRESSURE TEST IS OK 4.) OK FOR DRYWALL UPON BLDG. INSPECTOR APPROVAL.
08/23/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) MUST STRAP DOWN ALL COPPER DROP IN WALL 2.) HORIZONTAL VENTS MUST BE STRAPPED EVERY 4' 3.) OUTLET FOR SOLID INTERCEPTOR HAS OSTRUCTION OF FLOW @ OUTLET DUE TO BUSHING SEE SECTION 311.5 94 UPC. 4.) WOOD SHIMS ARE NOT APPROVED MATERIAL FOR SECURING COPPER. MUST USE APPROVED STRAPS. 5.) EXTERIOR ABS WASTE LINES MUST HAVE A MIN. 12" OF COVER FROM SUB GRADE. 4.) MUST TEST WASTE & VENT SYSTEM ALL THE WAY TO TOP OF VENT THRU ROOF. SEE SECTION 712.2 94 UPC 5.) GAS SYSTEM NOT TO APPROVED PLAN.